Registradores HOBO y Stowaway de Onset Computer

Novedades Onset

Revista HOBO News

Tablas Comparativas

Preguntas Frecuentes

Aplicaciones

Laboratorios Onset

Solicitar Información

Solicitar Catálogo General

 

HOBO® FlexSmart™ Logger System
Veris (kWh) Transducer

     

Veris 805x-series transducers are self-contained units incorporating split-core AC current sensors with processing electronics and voltage leads for monitoring kilowatt hours of energy used. The transducers provide pulse output of kWh, and interface with the HOBO FlexSmart Logger using a Pulse Input Adapter. Single-phase systems include 1 CT and 1 Voltage lead; 3-phase systems include 3 CTs and 3 voltage leads. Because these sensors tie directly into the line, they should be used only by qualified personnel.
Features and Specifications
   
Includes Split-Core Current Transformers (CT) and Voltage leads
Ranges and configurations:
• 208 to 480 VAC
• 300 Amps, 1-phase (T-VER-8051-300)
        (1 phase configuration PDF)

• 800 Amps, 3-phase (T-VER-8053-800)
         (3 phase configuration PDF)
 
Frequency: 50 to 60Hz
Accuracy: ±1% (3-phase model conforms to ANSI C12.1 metering standards)
CT range: 0-300 Amp (T-VER-8051-300); 0-800 Amp (T-VER-8053-800)
Circuit connection: 3- or 4-wire
Maximum output current: 100mA@24VAC/DC
Operating temp range: 0° to 60°C (32° to 140°F)
Operating humidity range: 0-95% RH (non-condensing)
Output signal to FlexSmart logger: Pulse (Normally open Opto-FET)
Pulse Width: 200 msec
Opening dimensions of each CT:
• T-VER-8051-300: 3.8 x 3.2 cm (1.5 x 1.25”)
• T-VER-8053-800: 7.3 x 6.2 cm (2.9 x 2.5”)
 
Requires Pulse Input Adapter (S-UCA-M006)

 

 

 

FlexSmart Logger and Modules

 

FlexSmart Analog

FlexSmart TRMS

 

Sensors

 

Corriente AC

Voltage AC

AC Watt Sensor

Kilowatt Hour KWH

Pressure

Presión Diferencial de Aire

Temp/H Relativa en conductos

Dióxido de Carbono

Pulse Input Adapter

8-Bits Temperature Smart Sensor

12-Bits Temperature Smart Sensor

Temp RH Smart Sensor

 

Software & Communication

 

HOBOware para Windows

Referencias para Pedidos

Descripción

Referencia

Pulse Input Adapter

 

Electronic Switch Version

S-UCA-M006

 

 

Killowatt Hour Transducer

 

208/240 VAC 3-phase Wye-connection kWh Transducer

T-WAT-3Y-208

480 VAC 3-phase Wye-connection kWh Transducer

T-WAT-3Y-480

208/240 VAC 3-phase Delta-connection kWh Transducer

T-WAT-3D-208

480 VAC 3-phase Delta-connection kWh Transducer

T-WAT-3D-480

The Pulse Input Adapter requires a HOBO FlexSmart, Weather Station, or Micro Station Data Logger for operation.

 

 

 

Equipos  Instrumentación  y  Control  S.L.

Urbanización Prado Norte, c/ Fresno  1 – bis  28110 Algete – MADRID

Telf.: 91 628 0817  Fax: 91 628 0453  Email: info@eiccontrol.com

Home |Productos Onset | Novedades | Contactar Comercialmente | Solicitar Información | Solicitar Catálogo Onset

Indice por Productos | Preguntas Frecuentes | Tablas Comparativas | Aplicaciones | Laboratorios Onset | Dónde Estamos